FJR Ingeniería Termomecánica
Back to projects Agribusiness in Paraguay

Air conditioning for a process room with a radio-frequency unit

A plant that treats seeds with a 125 kW radio-frequency unit needed to know how much cooling capacity the room required so operators could work in proper conditions.

Service
Heat load calculation
Floor area
150 m²
Total load
23.4 TR
Recommendation
25 TR or more

The challenge

The room, 150 m² in area and 5.5 m high, houses a radio-frequency unit for the thermal treatment of seeds and 4 operators per shift. The unit's metal surfaces radiate heat into the room, and one side of the room was noticeably hotter than the other.

The room already had outdoor air supply, dedicated process exhaust and positive pressure. What was missing was a reliable number: how much heat had to be removed to keep comfortable conditions, and with what kind of system.

What we did

  1. We reviewed the project information: equipment data sheets, operating conditions, room construction (insulated steel deck roof and prefabricated panel walls) and outdoor air supply flow (3,530 CFM).
  2. We set the design conditions using ASHRAE climate data for Asunción: 36 °C outdoor temperature and a target of 24 °C with 55 % relative humidity inside the room.
  3. We calculated each load with specialized HVAC load software: people, lighting, building envelope, the heat the radio-frequency unit releases into the room (25 kW) and the outdoor air load to be treated.
  4. We applied a 5 % safety factor and translated the result into equipment capacity and airflow.

Results

The room's total load is 281,252 Btu/h, equivalent to 82.4 kW or 23.4 TR. Removing the sensible heat requires a supply airflow of 9,769 CFM with a temperature difference of 20 °F (11.1 °C).

The key finding is where that load comes from: 88 % comes from the equipment and the outdoor air. The envelope, lighting and people contribute little. So the solution requires a system that can modulate against a dominant, variable load.

Breakdown of the total heat load (281,252 Btu/h) Equipment and ventilationEnvelopeLightingPeople 88 %7 %3 %1 %
The "equipment and ventilation" load includes the heat radiated by the radio-frequency unit and the load of the pressurization outdoor air.

Room layout

Radio-frequency unit 125 kW, releases 25 kW into the room hotter side outdoor air supply 3,530 CFM process exhaust 4 operators 150 m², 5.5 m high, positive pressure
Diagram prepared by FJR from the project information. It does not show the plant's exact layout.

Recommendation

Select equipment with a nominal capacity of 25 TR or more, and choose between two strategies depending on the plant's priority:

  • Adaptive comfort at 27 °C with active dehumidification: improves how warm operators feel and reduces the thermal shock when going outside.
  • Strict control at 24 °C: a system that removes the full load to hold the design temperature constantly.

Since ventilation accounts for about half of the load, we recommended a VRF system, which modulates precisely against variable loads, with distribution through high-static ducted indoor units or a dedicated closed-loop air handling unit.

Deliverables

  • Technical report in PDF with the sensible and latent load calculation.
  • Summary of the total load in kW and TR, with the required airflow.
  • Air conditioning alternatives and system recommendation.
  • Follow-up meeting to review the results.

Do you have a process room with temperature problems?

Tell us about your room and its equipment. We will help you find out what capacity you need before you buy.

Request a consultation